This message is for the use case when an implementation has detected a Lower Critical sensor going low
has asserted.
May also be shown as 800102041d02ffff or 0x800102041d02ffff
Severity
Error
Serviceable
Yes
Automatically notify support
No
Alert Category
Critical - Fan Failure
SNMP Trap ID
11
CIM Information
Prefix: PLAT ID: 0480
User Response
1. Reseat the failing fan n, which is indicated by a lit LED near the fan connector on the system
board.
2. Replace the failing fan. (n = fan number)
• 80010701-0701ffff : Numeric sensor [NumericSensorElementName] going high (upper non-critical)
has asserted. (PCI Temp)
This message is for the use case when an implementation has detected an Upper Non-critical sensor
going high has asserted.
May also be shown as 800107010701ffff or 0x800107010701ffff
Severity
Warning
Serviceable
Yes
Automatically notify support
No
Alert Category
Warning - Temperature
SNMP Trap ID
12
CIM Information
Prefix: PLAT ID: 0490
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear
of the server), that the air baffle is in place and correctly installed, and that the server cover is
installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
Lenovo System x3100 M5 Installation and Service Guide