No
Alert Category
Critical - Temperature
SNMP Trap ID
0
CIM Information
Prefix: PLAT ID: 0494
User Response
1. Make sure that the fans are operating, that there are no obstructions to the airflow (front and rear
of the server), that the air baffle is in place and correctly installed, and that the server cover is
installed and completely closed.
2. Check the ambient temperature. You must be operating within the specifications (see Server
Features and specifications for more information).
3. Make sure that the heat sink for microprocessor n.
4. (Trained technician only) Replace system board.
• 80010902-0701ffff : Numeric sensor [NumericSensorElementName] going high (upper critical) has
asserted.
This message is for the use case when an implementation has detected an Upper Critical sensor going
high has asserted.
May also be shown as 800109020701ffff or 0x800109020701ffff
Severity
Error
Serviceable
Yes
Automatically notify support
Yes
Alert Category
Critical - Voltage
SNMP Trap ID
1
CIM Information
Prefix: PLAT ID: 0494
User Response
If the specified sensor is Planar 3.3V or Planar 5V, (Trained technician only) replace the system board.
If the specified sensor is Planar 12V, complete the following steps until the problem is solved:
1. Check power supply n LED.
2. Remove the failing power supply.
3. (Trained technician only) Replace the system board. (n = power supply number)
• 80010b01-0701ffff : Numeric sensor [NumericSensorElementName] going high (upper non-
recoverable) has asserted. (PCI Temp)
This message is for the use case when an implementation has detected an Upper Non-recoverable sensor
going high has asserted.
Lenovo System x3100 M5 Installation and Service Guide