6.10 AIR FLOW FAULT TESTS

These tests check the operation of the Blower Proof Switch and Blocked Inlet Switch shown in
Figure 6-3.
1.
Disable the blower output drive voltage as follows:
(a) Press the MENU key until CONFIGUR-ATION MENU is displayed.
(b) Press the ▲ arrow key until the ANA-LOG OUTPUT function is displayed, then
press the CHANGE key.
(c) Press the ▼ arrow key until OFF is displayed, then press the ENTER key.
2.
Start the unit in the Manual Mode at a valve position of 34%.
3.
The unit should shut down and execute an IGNITION RETRY cycle by performing the
following steps:
(a) The unit will execute a 30 second re-ignition delay and display WAIT RETRY
PAUSE.