2.2 Mechanical Installation
Single Converter Installation
Figure 2.2
shows the installation distance required to maintain sufficient space for airflow and wiring. Install the
heatsink against a closed surface to avoid diverting cooling air around the heatsink.
Figure 2.2
Parallel Mounting with Drive
When installing the converter beside a drive, mount the devices according to
Figure 2.3
30
Side Clearance
Top/Bottom Clearance
A
B
B
A
A – 50 mm minimum
B – 30 mm minimum
Figure 2.2 Correct Installation Spacing (Single)
Side Clearance
Line up the tops of the drive and converter.
A
C
Converter
B
A
A – 50 mm minimum
B – 30 mm minimum
Figure 2.3 Space Between Converter and Drive (Parallel Mounting)
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
C
D
C
C – 120 mm minimum
D – Airflow direction
A
Drive
B
A
C – 60 mm minimum
D – 120 mm minimum
D
Figure
2.3.
Top/Bottom Clearance
D
D