YASKAWA CIMR-DC4A0040AAA Technical Manual page 180

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

B.2 Parameter Tables
No.
(Address
Name
Hex)
Power Supply
L2-36
Resonance
Detection Time
Number of Power
L2-37
Supply Resonance
Detection
L5-01
Number of Auto
(49EH)
Restart Attempts
Auto Restart Fault
L5-02
Output Operation
(49FH)
Selection
L5-04
Fault Reset Interval
(4A0H)
Time
L5-05
Fault Reset
(46CH)
Operation Selection
Active Current Limit
L7-25
at Power Supply
(628H)
Side
L7-26
Active Current Limit
(629H)
at Regeneration Side
L8-02
Overheat Alarm
(4AEH)
Level
L8-03
Overheat Pre-Alarm
(4AFH)
Operation Selection
L8-07
Input Phase Loss
(4B3H)
(PF3) Protection
Selection
<3>
L8-09
Output Ground Fault
(4B5H)
Detection Selection
Heatsink Cooling
L8-10
Fan Operation
(4B6H)
Selection
L8-11
Heatsink Cooling
(4B7H)
Fan Off Delay Time
L8-12
Ambient
(4B8H)
Temperature Setting
L8-35
Installation Method
(4ECH)
Selection
180
LCD Display
vrE Detect time
vrE Detect Count
L5: Fault Restart
Num of Restarts
Restart Sel
0: Flt Outp Disabld
1: Flt Outp Enabled
Flt Reset Wait T
Fault Reset Sel
0: Continuous
1: Use L5-04 Time
L7: Motoring Limit
Motoring I Limit
Regen I Limit
L8: Drive Protection
OH Pre-Alarm Lvl
OH Pre-Alarm Sel
1: Ramp to stop
3: Alarm only
Phase Loss Det
Grnd Flt Det Sel
0: Disabled
1: Enabled
Fan On/Off Sel
0: Dur Run (OffDly)
1: Always On
Fan Delay Time
Ambient Temp
Installation Sel
0: IP00/OpenChassis
1: Side-by-Side
3: ExternalHeatsink
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Description
There is normally no need to change this parameter from
the default value.
The converter will stop temporarily, if a power supply
resonance is detected (rvE).
The converter will stop completely, if a power supply
resonance is detected (rvE) within the time set in L2-36 in
milliseconds for the number of time that is set in L2-37.
Sets the number of times the converter may attempt to
restart after the following faults occur: GF, oC, oH1, oL2,
ov, Uv1.
0: Fault output not active.
1: Fault output active during restart attempt.
Sets the amount of time to wait between performing fault
restarts.
0: Continuously attempt to restart while incrementing
restart counter only at a successful restart.
1: Attempt to restart with the interval time set in L5-04 and
increment the
restart counter with each attempt.
Sets the limit for the active current at the power supply
side.
Sets the limit for the active current at the regeneration side.
An overheat alarm occurs when heatsink temperature
exceeds the L8-02 level.
1: Ramp to stop. A fault is triggered.
3: Continue operation. An alarm is triggered.
Enables or disables the condition of input current detection
for input phase loss (PF3). When L8-69 = 0, the PF3 fault
is disabled regardless of the L8-07 setting.
0: Disabled (Input phase loss detection (PF3) protection by
using input voltage)
1: Enabled (Input phase loss detection (PF3) protection by
using input voltage and current)
0: Disabled
1: Enabled
0: During run only. Fan operates only during run for L8-11
seconds after stop.
1: Fan always on. Cooling fan operates whenever the
converter is powered up.
Sets a delay time to shut off the cooling fan after the Run
command is removed when L8-10 = 0.
Enter the ambient temperature. This value adjusts the oL2
detection level.
0: IP00/IP20/Open Type Enclosure
1: Side-by-Side Mounting
3: External Heatsink Installation
Values
Default: 300 ms
Min.: 150 ms
Max.: 1000 ms
Default: 3
Min.: 1
Max.: 10
Default: 0 time
Min.: 0 time
Max.: 10 times
Default: 0
Min.: 0
Max.: 1
Default: 10.0 s
Min.: 0.5 s
Max.: 600.0 s
Default: 0
Min.: 0
Max.: 1
Default: 200%
Min.: 0%
Max.: 200%
Default: 200%
Min.: 0%
Max.: 200%
Default:
<2>
Min.: 50°C
Max.: 150°C
Default: 3
Min.: 1
Max.: 3
Default: 1
Min.: 0
Max.: 1
Default:
<2>
Min.: 0
Max.: 1
Default: 0
Min.: 0
Max.: 1
Default: 60 s
Min.: 0 s
Max.: 300 s
Default: 40°C
Min.: -10°C
Max.: 50°C
Default:
<2>
Min.: 0
Max.: 3