YASKAWA CIMR-DC4A0040AAA Technical Manual page 177

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

No.
(Address
Name
Hex)
H3-08
Terminal A3 Bias
(416H)
Setting
H3-09
Terminal A2 Signal
(417H)
Level Selection
H3-10
Terminal A2
(418H)
Function Selection
H3-11
Terminal A2 Gain
(419H)
Setting
H3-12
Terminal A2 Bias
(41AH)
Setting
H3-13
Analog Input Filter
(41BH)
Time Constant
Analog Input
H3-14
Terminal Enable
(41CH)
Selection
H3-
Function
Setting
F
Through mode
Power Supply Side Active
10
Current Limit
Regeneration side Active
12
Current Limit
19
Voltage Reference
No.
(Address
Name
Hex)
H4-01
Terminal FM
(41DH)
Monitor Selection
H4-02
Terminal FM
(41EH)
Monitor Gain
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
LCD Display
Sets the level of the input value selected in H3-06 when 0
Terminal A3 Bias
V is input at terminal A3.
0: 0 to 10 V
Term A2 Level
1: -10 to 10 V
0: 0-10V, (LowLim=0)
2: 4 to 20 mA
1: 0-10V, (BipolRef)
3: 0 to 20 mA
2: 4-20 mA
Note: Use DIP switch S1 to set input terminal A2 for a
3: 0-20 mA
current or a voltage input signal.
Term A2 FuncSel
Sets the function of terminal A2.
Sets the level of the input value selected in H3-10 when 10
Terminal A2 Gain
V (20 mA) is input at terminal A2.
Sets the level of the input value selected in H3-10 when 0
Terminal A2 Bias
V (0 or 4 mA) is input at terminal A2.
Sets a primary delay filter time constant for terminals A1,
A1/A2 Filter T
A2, and A3. Used for electrical noise filtering.
Determines which analog input terminals will be enabled
A1/A2 Sel
when a digital input programmed for "Analog input
1: A1 Available
enable" (H1- = C) is activated.
2: A2 Available
1: Terminal A1 only
3: A1/A2 Available
2: Terminal A2 only
4: A3 Available
3: Terminals A1 and A2 only
5: A1/A3 Available
4: Terminal A3 only
6: A2/A3 Available
5: Terminals A1 and A3
7: All Available
6: Terminals A2 and A3
7: All terminals enabled
H3 Analog Output Settings
LCD Display
Through mode
Motoring I Limit
Regen I limit
DC V Reference
LCD Display
H4: Analog Outputs
Selects the data to be output through terminal FM.
Set the desired monitor parameter to the digits available in
Term FM FuncSel
U-.
For example, enter "153" for U1-53.
Sets the signal level at terminal FM that is equal to 100% of the
Terminal FM Gain
selected monitor value.
Description
Description
Set this value when using the terminal in the pass-through mode.
10 V = Converter rated current
10 V = Converter rated current
10 V = Maximum value in d8-01
Note: The analog input 0 to 10 V is the same as the voltage
reference 0 V up to the maximum value in d8-01. The voltage
reference is limited to the minimum value in d8-01.
Description
B.2 Parameter Tables
Values
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
Default: 2
Min.: 0
Max.: 3
Default: F
Min.: F
Max.: 19
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
Default: 0.0%
Min.: -999.9%
Max.: 999.9%
Default: 0.03 s
Min.: 0.00 s
Max.: 2.00 s
Default: 7
Min.: 1
Max.: 7
Values
Default: 157
Min.: 000
Max.: 999
Default: 100.0%
Min.: -999.9%
Max.: 999.9%
177
B

Advertisement

Table of Contents
loading

Table of Contents