7.
Guide the lead wires through the provided hooks so the wires are held in place.
Figure 6.29
8.
Double-check the relay connector to ensure that it is properly connected.
Installing the Cooling Fan Unit
1.
Reverse the procedure described above to reinstall the cooling fan unit.
Figure 6.30
2.
Reattach the covers and digital operator.
3.
Turn on the power supply and set o4-03 to 0 to reset the Maintenance Monitor cooling fan operation time.
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Circuit Board Cooling Fan B6
Relay Connector
Figure 6.29 Cooling Fan Wiring: 4A0270, 4A0370
Figure 6.30 Install the Cooling Fan Unit: 4A0270, 4A0370
Circuit Board Cooling Fan B7
Hook
Relay Connector
6.4 Cooling Fans
6
143