6.5 Converter Replacement
4.
Disconnect all option cards and options. Make sure they are intact before reusing them.
5.
Replace the converter and wire the main circuit.
■
Installing the Converter
1.
After wiring the main circuit, connect the terminal block to the converter as shown in
installation screw to fasten the terminal block into place.
Figure 6.45
2.
Replace the terminal cover.
3.
Put the terminal cover back into its original place.
4.
When the power to the converter is first switched on, all parameter settings are transferred from the terminal
board into the converter memory. Should an oPE04 error occur, load the parameter settings that have been
saved on the terminal board onto the new converter by setting parameter A1-03 to 5550. Reset timers used for
the Maintenance Monitor function by setting parameters o4-01 through o4-12 back to 0, and parameter o4-13 to
1.
150
Figure 6.45 Installing the Terminal Board
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual