YASKAWA CIMR-DC4A0040AAA Technical Manual page 241

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

Wire Gauges and Tightening Torques
Table D.5 Wire Gauge and Torque Specifications (Three-Phase 200 V Class)
Model
Terminal
R/L1, S/L2, T/L3
– +
,
2A0005
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0010
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0020
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0030
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0050
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0065
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
2A0090
r1/ 11, 1/ 21, t1/ 31
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Recomm. Gauge
Applicable Gauge
AWG, kcmil
AWG, kcmil
12
12
14
10
8
8
14
10
4
4
14
6
2
2
14
4
3 × 2P
1/0 × 2P
1/0 to 2/0
14
4
3/0 × 2P
3/0 to 300
3/0 × 2P
3/0 to 300
14
1
3/0 × 2P
3/0 to 300
3/0 × 2P
3/0 to 300
14
1/0
1/0 to 4/0
Screw Size
12 to 6
M4
12 to 6
M4
14
M3.5
16 to 10
M6
8 to 6
M4
8 to 6
M4
14
M3.5
12 to 10
M6
4 to 1
M6
4 to 1
M6
14
M3.5
8 to 6
M6
2 to 2/0
M8
2 to 2/0
M8
14 to 10
M4
6 to 4
M8
3 to 2/0
M8
M8
14 to 10
M4
4
M10
M12
M12
14 to 10
M4
1 to 1/0
M12
M12
M12
14 to 10
M4
M12
D.3 UL Standards
Tightening Torque
Nm (lbin.)
2.1 to 2.3
(18.6 to 20.4)
2.1 to 2.3
(18.6 to 20.4)
0.8 to 1.0
(7.1 to 8.9)
5.4 to 6.0
(47.8 to 53.1)
2.1 to 2.3
(18.6 to 20.4)
2.1 to 2.3
(18.6 to 20.4)
0.8 to 1.0
(7.1 to 8.9)
5.4 to 6.0
(47.8 to 53.1)
3.6 to 4.0
(31.9 to 35.4)
3.6 to 4.0
(31.9 to 35.4)
0.8 to 1.0
(7.1 to 8.9)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
1.1 to 1.2
(9.7 to 10.6)
9.0 to 11
(79.7 to 97.4)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
1.1 to 1.2
(9.7 to 10.6)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
D
241