Model
Terminal
R/L1, S/L2, T/L3
– +
,
4A0060
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0100
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0130
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0185
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0270
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0370
r1/ 11, 1/ 21, t1/ 31
R/L1, S/L2, T/L3
– +
,
4A0630
r1/ 11, 1/ 21, t1/ 31
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Recomm. Gauge
Applicable Gauge
AWG, kcmil
AWG, kcmil
2
2
14
6
3 × 2P
1/0 × 2P
1/0 to 2/0
14
3
3/0 × 2P
3/0 to 600
3/0 × 2P
3/0 to 600
14
1/0
1/0 to 2/0
3/0 × 2P
3/0 to 600
3/0 × 2P
3/0 to 600
14
1/0
1/0 to 4/0
300 × 2P
300 × 2P
14
2/0
2/0 to 4/0
4/0 × 4P
4/0 to 300
4/0 × 4P
4/0 to 300
14
4/0
2/0 to 300
4/0 × 8P
4/0 to 300
4/0 × 8P
4/0 to 300
14
250
2/0 to 300
Screw Size
2 to 2/0
M8
2 to 2/0
M8
14 to 10
M4
6
M10
3 to 2/0
M8
M8
14 to 10
M4
3
M10
M10
M10
14 to 10
M4
M10
M12
M12
14 to 10
M4
M12
300
M12
300
M12
14 to 10
M4
M12
M12
M12
14 to 10
M4
M12
M12
M12
14 to 10
M4
M12
D.3 UL Standards
Tightening Torque
Nm (lbin.)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
1.1 to 1.2
(9.7 to 10.6)
18 to 23
(159 to 204)
5.4 to 6.0
(47.8 to 53.1)
5.4 to 6.0
(47.8 to 53.1)
1.1 to 1.2
(9.7 to 10.6)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
18 to 23
(159 to 204)
1.1 to 1.2
(9.7 to 10.6)
18 to 23
(159 to 204)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
32 to 40
(283 to 354)
1.1 to 1.2
(9.7 to 10.6)
32 to 40
(283 to 354)
D