B.2 Parameter Tables
◆ H: Multi-Function Terminals
H parameters assign functions to the multi-function input and output terminals.
No.
(Address
Name
Hex)
Multi-Function
H1-01
Digital Input
(438H)
Terminal S1
Function Selection
Multi-Function
H1-02
Digital Input
(439H)
Terminal S2
Function Selection
Multi-Function
H1-03
Digital Input
(400H)
Terminal S3
Function Selection
Multi-Function
H1-04
Digital Input
(401H)
Terminal S4
Function Selection
Multi-Function
H1-05
Digital Input
(402H)
Terminal S5
Function Selection
Multi-Function
H1-06
Digital Input
(403H)
Terminal S6
Function Selection
Multi-Function
H1-07
Digital Input
(404H)
Terminal S7
Function Selection
Multi-Function
H1-08
Digital Input
(405H)
Terminal S8
Function Selection
H1-
Function
Setting
1
LOCAL/REMOTE selection
8
Baseblock command (N.O.)
9
Baseblock command (N.C.)
C
Analog terminal input selection Term A2 Enable
F
Through mode
14
Fault reset
18
Timer function input
1B
Program lockout
174
LCD Display
H1: Multi-Function Digital Inputs
Term S1 Func Sel
Term S2 Func Sel
Term S3 Func Sel
Term S4 Func Sel
Term S5 Func Sel
Term S6 Func Sel
Term S7 Func Sel
Term S8 Func Sel
H1 Multi-Function Digital Input Selections
LCD Display
Local/Remote Sel
Ext BaseBlk N.O.
Ext BaseBlk N.C.
Term Not Used
Fault Reset
Timer function
Program Lockout
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Description
Assigns a function to the multi-function digital inputs S1
to S8.
Note: Set unused terminals to F.
Open: REMOTE (parameter settings determine the source of the frequency
Reference 1 or 2 (b1-01, b1-02 or b1-15, b1-16)
Closed: LOCAL, Frequency reference and Run command are input from
the digital operator
Closed: No converter output
Open: No converter output
Open: Function assigned by H3-14 is disabled.
Closed: Function assigned by H3-14 is enabled.
Select this setting when using the terminal in a pass-through mode.
Closed: Resets faults if the cause is cleared and the Run command is
removed.
Triggers the timer set up by parameters b4-01 and b4-02. Must be set in
conjunction with the timer function output (H2- = 12).
Open: Parameters cannot be edited (except for U1-01 if the reference
source is assigned to the digital operator).
Closed: Parameters can be edited and saved.
Default: 4B
Min.: 1
Max.: 67
Default: 4C
Min.: 1
Max.: 67
Default: 24H
Min.: 0
Max.: 67
Default: 14H
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: F
Min.: 0
Max.: 67
Default: 8H
Min.: 0
Max.: 67
Description
Values