YASKAWA CIMR-DC4A0040AAA Technical Manual page 175

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

H1-
Function
Setting
24 to 27
External fault
2C to 2F
47
Node Setup
Run Command
4B
(2-wire Sequence)
Stop Command
4C
(2-wire Sequence)
67
Communications test mode
No.
(Address
Name
Hex)
Terminal M1-M2
H2-01
function selection
(40BH)
(relay)
Terminal M3-M4
H2-02
Function Selection
(40CH)
(Relay)
Terminal M5-M6
H2-03
Function Selection
(40DH)
(Relay)
H2-06
kWh Monitor Pulse
(437H)
Output Unit Selection
H2-
Function
Setting
0
During run
6
Ready
7
DC bus undervoltage
8
During baseblock (N.O.)
E
Fault
F
Through mode
10
Minor fault
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
H1 Multi-Function Digital Input Selections
LCD Display
External fault
24: NO/ Always Det,
Coast to Stop
25: NC/Always Det,
Coast to Stop
26: NO/During RUN,
Coast to Stop
27: NC/During RUN,
Coast to Stop
2C: NO/Always Det,
Alarm Only
2D: NC/Always Det,
Alarm Only
2E: NO/ During RUN,
Alarm Only
2F: NC/During RUN,
Alarm Only
Node SetUp
Run Command3
Stop Command3
Comm Test Mode
LCD Display
H2: Multi-Function Relay Outputs
M1-M2 Func Sel
Refer to
P1/PC Func Sel
page 175
Note: Set unused terminals to F.
P2/PC Func Sel
Select the output unit of the multi-function contact when
Pwr Mon Unit Sel
H2-01 to H2-03 is set to 39 and 3A.
1: 1 kWh units
2: 10 kWh units
1: 1 kWh Units
3: 100 kWh units
2: 10 kWh Units
4: 1000 kWh units
3: 100 kWh Units
4: 1000 kWh Units
H2 Multi-Function Relay Output Settings
LCD Display
During RUN 1
Drive Ready
DC Bus Undervolt
BaseBlk 1
Fault
Not Used
Minor Fault
Description
24: N.O., Always detected, coast to stop
25: N.C., Always detected, coast to stop
26: N.O., During run, coast to stop
27: N.C., During run, coast to stop
2C: N.O., Always detected, alarm only (continue running)
2D: N.C., Always detected, alarm only (continue running)
2E: N.O., During run, alarm only (continue running)
2F: N.C., During run, alarm only (continue running)
Closed: Node setup for SI-S3 enabled.
Closed: Run
Note: To start operation, close the Stop Command (4C) and then open the
Run Command signal. After operation has started, it will continue even if
the Run Command signal is opened.
Open: Stop.
Note: To stop operation, open the Stop Command signal.
Tests the MEMOBUS/Modbus RS-422/RS-485 interface. Displays
"PASS" if the test completes successfully.
Description
H2 Multi-Function Relay Output Settings on
for a description of setting values.
Description
Closed: A Run command is active or voltage is output.
Closed: Power up is complete and the converter is ready to accept a Run
command.
Closed: DC bus voltage is below the Uv trip level set in L2-05.
Closed: Converter has entered the baseblock state (no output voltage).
Closed: Fault occurred.
Set this value when using the terminal in the pass-through mode.
Closed: An alarm has been triggered.
B.2 Parameter Tables
Values
Default: 25H
Min.: 0
Max.: 160
Default: 26H
Min.: 0
Max.: 160
Default: 6H
Min.: 0
Max.: 160
Default: 1
Min.: 1
Max.: 4
175