YASKAWA CIMR-DC4A0040AAA Technical Manual page 188

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

B.2 Parameter Tables
No.
(Address
Name
Hex)
U4-04
Cooling Fan
(7EH)
Maintenance
U4-05
Capacitor
(7CH)
Maintenance
Soft Charge
U4-06
Bypass Relay
(7D6H)
Maintenance
U4-08
Heatsink
(68H)
Temperature
U4-09
LED Check
(5EH)
U4-13
Peak Hold
(7CFH)
Current
DC BUS Voltage
U4-18
Reference Source
(7DAH)
Selection
U4-20
Option DC
(7DCH)
voltage Reference
Power Supply
U4-35
Module
(1042H)
Undervoltage
(Uv)
Power Supply
U4-36
Module
(1043H)
Overvoltage (ov)
Heatsink
U4-37
Overheat (oH)
(1044H)
Module
U4-38
Cooling Fan Error
(1045H)
(Fan) Module
U6-80 to
U6-99
Option Monitors
(7B0H to
1 to 20
7F9H)
U9-01
Electric Power
(820H)
(GWh)
U9-02
Electric Power
(821H)
(MWh)
U9-03
Electric Power
(822H)
(kWh)
188
LCD
Display
Displays main cooling fan usage time as a percentage of its expected
Fan Life
performance life. Parameter o4-03 can be used to reset this monitor.
Mon
Replace the fan when this monitor reaches 90%.
Displays main circuit capacitor usage time as a percentage of their
Cap Life
expected performance life. Parameter o4-05 can be used to reset this
Mon
monitor.
Replace the capacitor when this monitor reaches 90%.
Displays the soft charge bypass relay maintenance time as a percentage of
ChgCirc
its estimated performance life. Parameter o4-07 can be used to reset this
Life Mon
monitor.
Replace the soft charge bypass relay when this monitor reaches 90%.
Heatsink
Displays the heatsink temperature.
Temp
LED Oper
Lights all segments of the LED to verify that the display is working
Check
properly.
Current
Displays the highest current value that occurred during run.
PeakHold
Displays the source for the DC BUS voltage reference as XY-nn.
X: indicates which reference is used:
1 = Reference 1 (b1-01)
Y-nn: indicates the reference source
0-01 = Digital operator
Reference
1-01 = Analog (terminal A1)
Source
1-02 = Analog (terminal A2)
1-03 = Analog (terminal A3)
3-01 = MEMOBUS/Modbus communications
4-01 = Communication option card
8-01 = Depends on b1-18
Option Freq
Displays the DC bus voltage reference input by an option card (decimal). 0.01%
Ref
Displays the module where power supply Undervoltage (Uv) occurred in
UV Alarm
binary.
Axis
Note: This setting is available only in model 4A0630.
Displays the module where power supply Overvoltage (ov) occurred in
OV Alarm
binary.
Axis
Note: This setting is available only in model 4A0630.
OH Alarm
Displays the module where Heatsink Overheat (oH) occurred in binary.
Axis
Note: This setting is available only in model 4A0630.
FAN Alarm
Displays the module where Cooling Fan Error (Fan) occurred in binary.
Axis
Note: This setting is available only in model 4A0630.
U6: Operation Status Monitors
Shows the monitor information for Option Monitor 1 (876 hex) to 20 (8FF
hex).
This information is displayed when option cards are connected.
200 V Class: 100% = 400 Vdc
400 V Class: 100% = 800 Vdc
U8: Operation Status Monitors
GWh
Consumed
Shows the total amount of electric power.
000 000 000 kWh
MWh
Consumed
kWh
Consumed
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Description
U9-03
U9-02
U9-01
Analog
Output
Unit
Level
No signal
output
1%
available
No signal
output
1%
available
No signal
output
1%
available
10 V: 100°C
1°C
No signal
output
available
1 A
<6>
No signal
output
available
No signal
output
available
No signal
output
available
No signal
output
available
No signal
output
available
No signal
output
available
No signal
output
1GWh
available
No signal
output
1MWh
available
No signal
output
1kWh
available