YASKAWA CIMR-DC4A0040AAA Technical Manual page 229

Power regenerative converter
Hide thumbs Also See for CIMR-DC4A0040AAA:
Table of Contents

Advertisement

◆ CE Low Voltage Directive Compliance
This converter has been tested according to European standard IEC/EN 61800-5-1:2007, and it fully complies with the
Low Voltage Directive.
To comply with the Low Voltage Directive, be sure to meet the following conditions when combining this converter with
other devices:
Area of Use
Do not use converter in areas with pollution degree 2 and overvoltage category III in accordance with IEC/EN 60664.
Standard Configuration Devices
Install appropriate Branch Circuit Protection to the input side to protect converter wiring and prevent other secondary
damage. Select harmonic filter module according to
Refer to
Power Ratings on page 162
NOTICE: If a fuse is open or a Residual Current Device (RCD) is tripped, check the wiring and the selection of peripheral devices to
identify the cause. Contact Yaskawa before restarting the converter or the peripheral devices if the cause cannot be identified.
Harmonic
Model
Filter
Module
Model
EUJ71080 350GH-25ULTC
2A0005
EUJ71081 350GH-50ULTC
2A0010
EUJ71082 350GH-125ULTC
2A0020
EUJ71083
170M1369
2A0030
EUJ71084 350GH-250ULTC
2A0050
EUJ71085
170M4012
2A0065
EUJ71086
170M4013
2A0090
EUJ71087
170M4017
2A0130
EUJ71088 660GH-16ULTC
4A0005
EUJ71089 660GH-40ULTC
4A0010
EUJ71090 660GH-63ULTC
4A0020
EUJ71091
170M1368
4A0030
EUJ71092
170M1369
4A0040
EUJ71093 660GH-160ULTC
4A0060
EUJ71094 660GH-250ULTC
4A0100
EUJ71095
170M4012
4A0130
EUJ71096
170M4015
4A0185
YASKAWA ELECTRIC SIEP C710656 06F YASKAWA Power Regenerative Converter - D1000 Technical Manual
Table D.1
for details on the converter Input Current and Rated Output Current.
Table D.1 Recommended Standard Configuration Devices
Input Fuse
Fuse Rating
Manufacturer
Ampere
(A)
HINODE
25
HINODE
50
HINODE
125
BUSSMANN
160
HINODE
250
BUSSMANN
400
BUSSMANN
450
BUSSMANN
700
HINODE
16
HINODE
40
HINODE
63
BUSSMANN
125
BUSSMANN
160
HINODE
160
HINODE
250
BUSSMANN
400
BUSSMANN
550
to
Table
D.3.
Three Phase Input AC Reactor
SAO ELECTRIC CORP.
Model
Ratings
200 V Class
15 A, 0.81 mH,
300-052-260
264 V
29 A, 0.42 mH,
300-052-261
264 V
57 A, 0.21 mH,
300-052-262
264 V
83 A, 0.15 mH,
300-052-263
264 V
140 A, 0.09 mH,
300-052-264
264 V
200 A, 0.06 mH,
300-052-265
264 V
270 A, 0.04 mH,
300-052-266
264 V
400 A, 0.03 mH,
300-052-267
264 V
400 V Class
8 A, 3.31 mH,
300-052-268
528 V
16 A, 1.65 mH,
300-052-269
528 V
30 A, 0.88 mH,
300-052-270
528 V
43 A, 0.62 mH,
300-052-271
528 V
58 A, 0.46 mH,
300-052-272
528 V
86 A, 0.31 mH,
300-052-273
528 V
145 A, 0.18 mH,
300-052-274
528 V
210 A, 0.13 mH,
300-052-275
528 V
300 A, 0.09 mH,
300-052-276
528 V
D.2 European Standards
Three Phase Input Film
Capacitor
Nichicon Corp.
Model
Ratings
EM161050S0UA1HN
160 VAC, 5 uF
EM161090S0UA1HN
160 VAC, 9 uF
EM161180S0UA1HS 160 VAC, 18 uF
EM161370S1UA1HZ 160 VAC, 12.5 uF
EM161281S1UA1HZ 160 VAC, 96 uF
EM161421S1UA1HZ 160 VAC, 140 uF
EM161551S1UA1HZ 160 VAC, 185 uF
EM161421S1UA1HZ 160 VAC, 140 uF
EM3211R2S0UA1HP 320 VAC, 1.2 uF
EM3217R5S1UA1HZ 320 VAC, 2.5 uF
EM3217R5S1UA1HZ 320 VAC, 2.5 uF
EM321090S1UA1HZ 320 VAC, 3 uF
EM321270S1UA1HZ 320 VAC, 9 uF
EM321390S1UA1HZ 320 VAC, 13 uF
EM321151S1UA2HZ 320 VAC, 50 uF
EM321101S1UA1HZ 320 VAC, 35 uF
EM321151S1UA2HZ 320 VAC, 50 uF
D
229

Advertisement

Table of Contents
loading

Table of Contents