Full Charge Feature Configuration; Setting The Full Charge Feature Parameters; Figure 5- 16 Full Charge Setup Screens - Webasto SVS100 Installation, Operation And Maintenance Manual

Gse intelligent fast charging systems
Table of Contents

Advertisement

5.10.6 Full Charge Feature Configuration

The charger can be configured to allow a window of time per day to fully charge the battery.
This is useful if there is a period of time when the batteries can be left on the charger without
limiting other batteries from charging (after-hours, lunch breaks, etc.) If the feature is enabled,
the connected battery will be allowed to charge up to 100% SOC whenever the charger clock
reads between the start and stop time.
In addition, a "topping-off" function can be programmed at the end of full charge that continues
to charge the battery at a reduced rate past the 100% point. This acts as a mini-equalization
that can benefit battery life and capacity.
5.10.6.1

Setting the Full Charge Feature Parameters

From the "Full/Overcharge Setup" screen press <enter> to display the Full Charge Enable
status. Press <enter> again and the status (ON or OFF) will flash. Press <up> or <down> to
toggle between ON and OFF. Press <enter> again to accept your selection. The remaining
screens in this section are accessed by pressing the <select> button. From the "Full Charge
Enable" screen, press <select> to display the "Full Charge Start Time" status. Press <enter> to
edit the start time and press <enter> again to fix your selection in memory. Press <select> to
display the "Full Charge End Time" screen. Press <enter> to edit the charge time using the
<up> and <down> buttons. Press <enter> to accept edited value. Press <select> to move to
the "Overcharge Period" screen and use the <enter>, <up>, and <down> buttons as before to
edit. Remember to press <enter> to save your edits. Once you have pressed <enter> to save
your edit, the display will stop flashing.
Full Charge
Setup
Full Charge Enable:
CLEAR
ON
Full Chrg Start time
02:00
Full Chrg End time
06:00
Low Current Period:
0.50 Hours
23435-W-03-01
SVS100 Installation, Operation and Maintenance Manual
ENTER
ENTER
SELECT
ENTER
SELECT
ENTER
SELECT
ENTER
SELECT

Figure 5- 16 Full Charge Setup Screens

38
Charger Configuration
CLEAR
Full Charge Enable:
OFF
SELECT
Press ENTER and use the UP and
DOWN arrow buttons to set the
parameter to the appropriate value.
Press ENTER again to accept the
selection made.
Press CLEAR to retain the original
value
Webasto Charging Systems, Inc.
CLEAR

Advertisement

Table of Contents
loading