When function setting is "Emergency stop" mode
z
In the case of "Edge" input
Connector
Ch1 of
CNA01 or CNA02
Ch1 input of
On
CNA01 or
Off
CNA02
Emergency stop
Command
Normal
Operation
Indoor unit
Stop
Remote
Controller
In the case of "Pulse" input
Connector
CNA01 or CNA02
Ch1 input
CNA01
or
CNA02
Ch2 input
Emergency stop
Command
Operation
Indoor unit
Remote
Controller
NOTE :
All indoor units of same refrigerant system stops when Emergency stop operates.
Input signal
Command
OFF → ON
Emergency stop
ON → OFF
Normal
On
Input signal
Ch1
OFF → ON
Ch2
OFF → ON
The width of pulse must be longer than 200msec.
On
Off
On
Off
Normal
Stop
- (08 - 12) -
On
On
Command
Emergency stop
Normal
On
On
On