1-3.

RB UNIT

External input

Cooling priority/
Heating priority
1-3-1.
EXTERNAL INPUT
RB unit can be cooling priority/heating priority selection by using RB unit PCB CNA01 or CNA02.
The "external input priority mode" must be set by changing DIP SW on PC board of RB unit.
A twisted pair cable (22AWG) should be used. Maximum length of cable is 150m.
Use an external input cable with appropriate external dimension, depending on the number of cables to be
installed.
The wire connection should be separate from the power cable line.
INPUT SELECT
Use either one of these types of terminal according to the application. (Both types of terminals
cannot be used simultaneously.)
Dry contact terminal ([CNA01])
z
When a power supply is unnecessary at the input device you want to connect, use the Dry
contact terminal ([CNA01]).
*a
connected unit
*a: Select very low current use contacts (usable at DC12V, DC1mA or less).
*b: The wiring is different from Apply voltage terminals. Be sufficiently careful when wiring.
External output
Input select
Dry contact
-
Apply voltage
- (08 - 25) -
Connector
CNA01
CNA02
P.C.B
1
CNA01
2
GND
*b
External connect kit

(Optional parts)

UTY-XWZXZ6
UTY-XWZXZB