Fujitsu AIRSTAGE J-II Design & Technical Manual page 666

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2-18.
NETWORK CONVERTOR FOR L
SWITCH POSITION
D19
JP1
SW3 SW4
ADDRESS SETTING
When setting address, please be sure that the address of Network Convertor for
L
W
is not overlap the address of other controller like, Touch Panel Controller,
ORKS ®
ON
Central Remote Controller & Network Convertor for Group Remote Controller.
Following steps are necessary for setting address of Network Convertor.
1) Turn on the power of network convertor.
2) Select the special mode by pressing and releasing SW7 (reset button) while holding down
SW4 (set button) until special mode "1" is displayed.
Special mode changes from '1' to '4' as shown in the above mentioned way.
3) Press SW3 (mode button) to set special mode "2". Special mode "2" is the address setting
mode.
4) Press SW4 (set button). Present address is displayed.
5) Press SW3 (mode button) to select the address. The displayed address changes as follows
each time the mode button is pressed.
A00
A01
A02
6) Press SW4 (set button) to set the selected address.
7) Turn the power off and on or press SW7 (reset button) to exit from address setting mode.
Anyone of the following indication will disappear:
: VRF Network address allocation is not registered by using Tool for Network Convertor
: Binding and Commissioning is not executed
: Normal Mode ( Ready for operation)
: Others (Please check Installation Manual for more detail)
SW1
SW2
SW7
Ex.) Address No. 15 is factory setting.
A15
Ex.) Address No. 3 is selected.
- (07-140) -
W
ORKS ®
ON
Ex.) Address No. 3 is set.