Fujitsu AIRSTAGE J-II Design & Technical Manual page 595

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Switching
between
2
0
batch stop or
emergency stop
Operation
2
1
mode selecting
method
Snow falling
2
2
protection fan
mode
Interval setting
for snow falling
2
3
protection fan
mode
High static
2
4
pressure mode
2
5
Prohibited
*1: Do not set this for outdoor units with Slave setting.
LED104
Setting Function
CODE No.
0
0
Batch stop
0
1
Emergency stop
Priority given to the
0
0
first command
Priority given to
0
1
external input of
outdoor unit
Priority given to
0
2
administrative indoor
unit
0
0
Valid
0
1
Invalid
0
0
Standard (30minutes)
0
1
Short1 (5minutes)
0
2
Short2 (10minutes)
0
3
Short3 (20minutes)
0
0
Standard
High static pressure 1
0
1
(equivalent to 30Pa)
High static pressure 2
0
2
(equivalent to 82Pa)
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
- (07-69) -
Outdoor unit
Factory
setting
Master Slave
This mode selects the pattern of
the stop function to be operated
by the external input terminal
(CN134).
l
•Batch stop: The stop of all
indoor units connected to same
refrigerant system due to input
signal coming from CN134.
-
¡
•Emergency stop: When
*1
emergency stop is actuated, the
indoor unit does not accept the
operation command from the
remote controller. On the other
hand, when the emergency
stop is released (no input from
CN134), the air conditioner
does not return to the original
operation until operate indoor
unit by the remote controller.
Select the priority setting of the
operation mode.
•Priority given to the first
l
command: Priority is given to
the operation mode which is set
first.
•Priority given to external input
of outdoor unit: Priority is given
-
to the operation mode which is
¡
*1
set by the external input terminal
(CN132).
•Priority given to administrative
indoor unit: Priority is given
to the operation mode of the
administrative indoor unit which
is set by the wired remote
controller.
This mode operates the fans
l
of outdoor units in order to
-
prevent the units from stopping
¡
*1
operation when they are
covered by snow.
l
When the snow falling protection
-
fan mode is set, the operation
¡
*1
interval of the fans of outdoor
units can be selected.
When installing a duct to the
l
blow-off outlet of an outdoor
unit, set the high static pressure
mode according to the static
pressure of the duct to be
¡
¡
installed.
Furthermore, use this setting if
the air blow of an outdoor unit is
poor, such as when installed in
a place with a low ceiling.
l
Setting prohibited
Remarks

Advertisement

Table of Contents
loading

Table of Contents