Fujitsu AIRSTAGE J-II Design & Technical Manual page 609

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

LED105
Setting Mode
CODE No.
Switching
between
2
0
batch stop or
emergency stop
Operation
2
1
mode selecting
method
2
2
Prohibited
2
3
Prohibited
2
4
Prohibited
2
5
Prohibited
LED104
Setting Function
CODE No.
0
0
Batch stop
0
1
Emergency stop
Priority given to the
0
0
first command
Priority given to
0
1
external input of
outdoor unit
Priority given to
0
2
administrative indoor
unit
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
- (07-83) -
Factory
Remarks
setting
This mode selects the pattern of the stop
function to be operated by the external input
terminal (CN134).
l
•Batch stop: The stop of all indoor units
connected to same refrigerant system due to
input signal coming from CN134.
•Emergency stop: When emergency stop is
actuated, the indoor unit does not accept the
operation command from the remote controller.
On the other hand, when the emergency
stop is released (no input from CN134), the
air conditioner does not return to the original
operation until operate indoor unit by the remote
controller.
l
Select the priority setting of the operation
mode.
•Priority given to the first command: Priority is
given to the operation mode which is set first.
•Priority given to external input of outdoor unit:
Priority is given to the operation mode which is
set by the external input terminal (CN132).
•Priority given to administrative indoor unit:
Priority is given to the operation mode of the
administrative indoor unit which is set by the
wired remote controller.
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited
l
Setting prohibited