SETTING EXAMPLE
●
Outdoor unit setting
SetA: Refrigerant circuit address
(Rotary SW REF AD x10, x1)
SetB: Outdoor unit address
SetA
SetB
(DIP SW SET3-1, 3-2)
00
0
SetC: Number of slave unit
SetC
SetL
(DIP SW SET3-3, 3-4)
2
3
<Master unit only>
SetL: Number of outdoor units
installed
(DIP SW SET5-1, 5-2)
●
Touch panel controller setting
SetG: Controller address (Max.16)
●
Network convertor setting
SetH: Convertor address
(for Group remote controller:Max.16)
Refrigerant circuit address
(for Single split AC:Max.100)
●
Central remote controller setting
SetN: Controller address (Max.16)
●
Group remote controller setting
SetI: Group remote controller address
(Max.4)
●
Signal amplifier setting
SetK: Signal amplifier address
Instructions for setting up the address
¾
1. The refrigerant circuit address of the indoor units, outdoor units and RB units can be set to arbitrary numbers in the
range of 0 to 99.
2. The Indoor unit address and RB unit address can be set to arbitrary numbers in the range of 0 to 63.
3. In case of 3-wire type of R.C., set the remote controller address in the order of 0,1,2, . . . ,15.(Blank is not allowed)
4. In case of 2-wire type of R.C.(Automatic address setting), set the remote controller address in the 0.
5. In case of 2-wire type of R.C.(Manual address setting), can be set to arbitrary numbers in the range of 1 to 15.
Can not be set to 0.
6. Touch panel controller address can be set to arbitrary numbers in the range of 0 to 15.
7 : The sum total of the Touch panel controller, Central remote controller, Network convertor for Group remote controller
and Network convertor for L
8. Please keep Address No. of Touch Panel Controller from overlapping the controller (Central remote controller,
Network convertor for Group remote controller and Network convertor for L
Network system.
●
Indoor unit setting
SetD SetE SetF
63
circuit address
REF AD X10 REF AD X1
RB unit setting
●
SetO SetP
63
circuit address
REF AD X10 REF AD X1
●
Wired, Simple remote controller (3-wire) setting
SetJ: Dual remote control
●
Network convertor for L
SetM: Convertor address
●
Wired remote controller (2-wire) setting
SetF: Remote controller address
W
® is a maximum of 16.
ON
ORKS
- (07-06) -
06
0
SetD
Refrigerant
Indoor unit
address
IU AD X10
06
SetO
Refrigerant
RB unit
address
RB AD X10
(SW2 of DIP Switch1)
ON
W
®) connected to the same VRF
ON
ORKS
SetE
SetF
Remote
controller
address
IU AD X1
RC AD
SetP
RB AD X1
W
setting
ORKS ®