J-Ii Series - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

2-1-4.

J-II series

SETTINGS LIST
LED105
Setting Mode
CODE No.
Pipe length
0
0
setting
1
0
Prohibited
Cooling
1
1
capacity shift
Heating
1
2
capacity shift
1
3
Prohibited
1
4
Prohibited
Switching
between
2
0
batch stop or
emergency stop
LED104
Setting Function
CODE No.
0
0
Standard (40 to 65m)
0
1
Short (less than 40m)
0
2
Medium (65 to 90m)
0
3
Long 1 (90 to 120m)
0
4
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
0
Normal mode
0
1
Save energy mode 1
0
2
High power mode 1
0
3
High power mode 2
0
4
Prohibited
0
0
Normal mode
0
1
Save energy mode
0
2
High power mode 1
0
3
High power mode 2
0
0
Prohibited
0
1
Prohibited
0
0
Prohibited
0
1
Prohibited
0
2
Prohibited
0
3
Prohibited
0
4
Prohibited
0
0
Batch stop
0
1
Emergency stop
- (07-77) -
Factory
Remarks
setting
l
Pipe length means the length between outdoor
unit and the nearest indoor unit.
l
Setting prohibited
l
l
l
Setting prohibited
l
Setting prohibited
This mode selects the pattern of the stop
function to be operated by the external input
terminal (CN134).
l
•Batch stop: The stop of all indoor units
connected to same refrigerant system due to
input signal coming from CN134.
•Emergency stop: When emergency stop is
actuated, the indoor unit does not accept the
operation command from the remote controller.
On the other hand, when the emergency
stop is released (no input from CN134), the
air conditioner does not return to the original
operation until operate indoor unit by the remote
controller.