Step 4 : Confirm how to install Signal Amplifier
z
When Signal Amplifier is installed, network is divided into two network segments.
In a network segment (NS) divided by a Signal Amplifier, it has to keep the following facts.
1)Total transmission line length: MAX 500 m
AB+BC+BD < 500 m (Fig. 2)
2)The total number of units *1 : MAX 64
3)The number of terminal resistor : 1
*1: Refer detail Meaning of unit on 1-2 VRF NETWORK SYSTEM.
Terminal
resistor
Outdoor unit
B
A
D
Indoor unit
When AB+BC+BD+DE+EF>500m
:Signal Amplifier is required.
Step 5 : Confirm how to wire transmission line
z
Confirm how to connect transmission line between indoor units.
Arrange so that there is one terminal resistor for each network segment.
Always take a ground from both ends of transmission line.
Transmission line
X1 X2
TRANS-
MISSION
Indoor unit
Step 6 : Confirm transmission wiring system
z
Check your transmission wiring system if the transmission wiring system is ensured wiring rule.
Check list
□ Total Transmission wiring length
□ Total number of unit *1
*1: Refer detail Meaning of unit on 1-2 VRF NETWORK SYSTEM.
Fig. 1
Transmission line
System
C
Controller
E
F
Touch
Panel
Controller
X1 X2
TRANS-
MISSION
Indoor unit
- (06 - 53) -
Fig. 2
Terminal
resistor
Outdoor unit
A
Transmission line
B
D
Terminal resistor
E
G
NS 3
Signal Amplifier
Indoor unit
NS 1
Touch
C
Panel
Controller
NS 2
F
System
Controller
NS 4
H