4-4.

CONTROLLER CABLE WIRING

WIRING SPECIFICATIONS
Model type
System Controller
USB Adaptor
System Controller
USB Adaptor
Lite
Touch Panel
Transmission line
Controller
Central Remote
Transmission line
Controller
Group Remote
Network Convertor
Controller
Wired Remote
Controller
Indoor unit
(UTY-RNR*) *2
Wired Remote
Controller
Indoor unit
(UTY-RLR*) *2
Wired Remote
Controller
Indoor unit
(UTY-RNK*)
Simple Remote
Indoor unit
Controller
Indoor unit
External Switch
Controller
External input
IR Receiver Unit
Indoor unit
(UTB-*WC)
IR Receiver Unit
Indoor unit
(UTY-LRH*B1)
Remote Sensor
Indoor unit
EV Kit
Indoor unit
Drain Pump Unit
Indoor unit
*1 : Use shielded cable (field supplied) in accordance with the regional cable standard.
*2 : Refer to next page
Install in accordance with the regional standard.
Never bundle the power supply cable and controller cable together. Bundling these cords together
will cause misoperation.
Always ground for shilded cable both end.
For detail specification and connection, please refer to "Chapter 5 CONTROL SYSTEM".
Controller might be required to connect power supply cable and transmission line. Use separate
connection with other units for power suply cable.
Connection to
USB cable
USB cable
Remote controller
cable
Remote controller
cable
Remote controller
cable
Connection cable
Connection cable
Connection cable
Connection cable
Connection cable
Wire
Size
-
-
0.33mm
0.33mm
to
1.25mm
0.33mm
0.33mm
0.33mm
-
-
-
-
-
Caution
- (06 - 58) -
Specification
Refer to 6-4-3
Refer to 6-4-3
2
Shielded, Polar 3core
2
Sheathed, Non-polar 2core,
Twisted pair *1
2
Sheathed PVC cable Polar
2
3core *1
2
Shielded, Polar 3core
Shielded, Polar 2core,
2
Twisted pair
(5m cable attached)
(10m cable attached)
(5m cable attached)