2-2.
PIPING LIMITATION
LIMITATION
a
c
Total pipe length
Between outdoor unit and the farthest indoor unit
Between the first separation tube and the farthest
indoor unit
Between outdoor unit and the nearrest indoor unit
Between outdoor unit and the first seperation tube
Between outdoor unit and indoor unit
Between indoor unit
1 : Total pipe length is limited by the condition that total refrigerant amount should not exceed 15.7kg.
b
Limitation
- (06 - 15) -
H
1
H
2
Diagram
180m or less *
Total
1
120m or less
a + b
40m or less
b
5m or more
a + c
3m or more
a
30m or less
H1
15m or less
H2