Fujitsu AIRSTAGE J-II Design & Technical Manual page 429

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

DIMENSIONS
30
18
5 - ø7
Left view
INSTALLATION
Connection Pattern
z
NOTE: Connection pattern is different according to type of Indoor unit.
Indoor unit types
All Cassette type
All Duct type
All Ceiling type
Wall Mounted type
Pattern A
z
Connect the end of remote controller cable directly to the exclusive terminal block.
Set the DIP switch (SW1) to "3WIRE" on the PC board of the indoor unit.
Terminal block
Functional earthing
Red
(If necessary)
Remote controller
White
cable
Black
* Layout of terminal block and
PC board is varies, depending
on the type of indoor unit.
NOTE: The equipment may fail if it is connected to the outdoor unit or the power supply
terminal block.
Pattern B
z
1) Use a tool to cut off the terminal on the end of the remote controller cable, and then
remove the insulation from the cut end of the cable as shown in Fig. 1. Connect the
remote controller cable and connecting cable as shown in Fig. 2. Be sure to insulate the
connection between the cables.
F
g i
1 .
F
g i
20 mm
Insulated
connection
Remote
controller cable
75
60
Front view
Rear view
Connection Pattern
Pattern A
Pattern B
Indoor unit
PC board
Set to "3WIRE" the
DIP switch (SW1)
2 .
White
Connecting
cable
Red
Black
- (05 - 125) -
(Unit: mm)