2-20-1.
SETTING METHOD
WIRED R.C.(Touch panel)
Step1: RB unit function setting (Case of VR-II series)
z
Please set SET2 of DIP switch to "Priority given to administrative indoor unit" with function
setting of RB unit. (SET2-1:OFF, SET2-2:ON)
→Refer to 2-7.RB UNIT
Step1: Outdoor unit function setting (Case of V-III or V-II or J-II or J-IIS
z
series)
Please set to "Priority given to administrative indoor unit" with function setting of outdoor unit.
→Refer to 6-1.OUTDOOR UNIT
Step2: Wired remote controller setting
z
1) Touch the [Master Indoor Unit Setting] on the
"Initial Setting" screen.
Initial Setting
R.C. Sensor
Master Indoor
Setting
Unit Setting
Password Setting
Previous
Back
Page
3) When the [Yes] is touched, after the data
is transmitted to the indoor unit, the display
returns to the "Master Indoor Unit Setting"
screen.
Master Indoor Unit Setting
The connected indoor unit will be
set as the master indoor unit. OK?
No
Note:
● When changing the Master Indoor Unit, first cancel the setting of the indoor unit currently set as the Master Indoor
Unit. Otherwise, an other indoor unit cannot be registered as the Master Indoor Unit newly..
Page 2/ 3
Display Item
Setting
Next
Page
Yes
2) "Master Indoor Unit Setting" screen is displayed.
When the [Set] is touched, a verification screen is
displayed.
Master Indoor Unit Setting
Master Indoor Unit Setting
Not Master Indoor Unit
Back
4) When the [Back] on the "Master Indoor Unit
Setting" screen is touched, the display returns to
the "Initial Setting" screen.
Master Indoor Unit Setting
Master Indoor Unit Setting
Master Indoor Unit Setting
Master Indoor Unit Setting
Master Indoor Unit
Master Indoor Unit
Back
Back
Reset
Reset
*1: To clear a master indoor unit, touch [Reset]. ("Reset" cannot
be performed while the indoor unit is operating.)
- (07-144) -
Set
*1