High Flowrate Alarm (2.8.9.) - Siemens SITRANS L 7ML5400 Operating Instructions Manual

Ultrasonic level controllers
Table of Contents

Advertisement

Parameter reference (LUI)
9.2 Setup (2.)
Assigned Relay (2.8.8.2.)
Determines which relay (if any) will be activated when the Fail-safe Alarm activates.
Options
Alarm State (2.8.8.3.)
Read only. Used to view the current state of the Fail-safe Alarm.
Options
9.2.8.9

High Flowrate Alarm (2.8.9.)

Available only on LUT440 (OCM model).
Reported when the OCM flowrate is within a user-defined range (see High Flowrate Value ON
(2.8.9.2.) (Page 208) and High Flowrate Value OFF (2.8.9.3.) (Page 208)).
Enable (2.8.9.1.)
Enables/disables High Flowrate Alarm.
Options
High Flowrate Value ON (2.8.9.2.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 238)) at which the High
Flowrate Alarm will activate.
Values
High Flowrate Value OFF (2.8.9.3.)
Sets the flowrate value (defined in Flowrate Units (2.15.3.7.) (Page 238)) at which the High
Flowrate Alarm will de-activate.
Values
208
*
ACTIVE
INACTIVE
*
Range: 0.000 to 99999.000
Default: 0.000
Range: 0.000 to 99999.000
Default: 0.000
Operating Instructions, 04/2021, A5E33329501-AG
NO RELAY
RELAY 1
RELAY 2
RELAY 3
ENABLED
DISABLED