Siemens SITRANS L 7ML5400 Operating Instructions Manual page 74

Ultrasonic level controllers
Table of Contents

Advertisement

Commissioning
6.3 Quick Start Wizards
Flowrate Units
The volume units used to display total flow.
Options
* If USER DEFINED option selected, the value must be set after completing the wizard. See
User Defined Unit (2.15.3.8.) (Page 239).
Maximum Flow at 20 mA
The maximum flowrate.
Value
Flowrate Decimal
The maximum number of decimal units to be displayed.
Options
Low Flow Cutoff
Eliminates totalizer activity for head levels at or below the cutoff value.
Value
End of QS Volume Wizard
For QS to be successful, all changes must be applied.
Options
To transfer Quick Start values to the device and return to Program menu, press DOWN arrow
(Finish). Then press LEFT arrow
Note
It is strongly recommended that an Auto Zero Head be performed after completion of the
wizard to ensure best accuracy. See Auto Zero Head (2.15.2.) (Page 235).
74
L/S, L/MIN, CUFT/S, CUFT/D, GAL/MIN, GAL/D, IMPGAL/MIN, IMPGAL/D, CUM/H, CUM/D,
MMGAL/D, USER DEFINED *
Default: L/S
Range: -999 to 9999999
Default: 100
NO DIGITS, 1 DIGIT, 2 DIGITS, 3 DIGITS
Default: NO DIGITS
Range: 0.000 to 60.000
Default: 0.000
BACK, CANCEL, FINISH
(Display returns to 1.1 Quick Start menu when Quick Start is successfully completed or
cancelled. If CANCEL is selected, no changes are written to the device.)
three times to return to Measurement mode.
Operating Instructions, 04/2021, A5E33329501-AG