Siemens SITRANS L 7ML5400 Operating Instructions Manual page 279

Ultrasonic level controllers
Table of Contents

Advertisement

Symptom
Incorrect reading (mA output
and/or displayed value)
Relay not activating
Relay not activating correctly
No response when echo profile
requested via LUI (Echo Profile
(3.2.1.) (Page 246))
Configuration error 130 dis-
played
SITRANS LUT400
Operating Instructions, 04/2021, A5E33329501-AG
Possible Cause
Noise in the application
mA function not assigned to
correct measurement
When device configured for
flow: exponent or breakpoint
not correctly selected
Incorrect vessel or PMD dimen-
sions
Relay not programmed
Relay incorrectly assigned
Incorrect relay function selected
Incorrect relay setpoints
Relay incorrectly assigned
Incorrect relay function selected
Incorrect relay setpoints
Transducer is disabled.
Relay/pump configuration errors
- possible causes include:
A relay is assigned to more
than one function (e.g. relay
2 is assigned to both an ex-
ternal totalizer and a pump).
Pump setpoints are out of
order.
Wall Cling adjustment range
is too large.
Diagnosing and Troubleshooting
11.4 Common Problems Chart
Action
Verify source and minimize. See
Noise Problems (Page 280).
Check mA assignment. See Cur-
rent Output Function (2.5.1.)
(Page 180).
Check configuration: if Sensor
Mode (2.1.2.) (Page 173) set to
FLOW, verify correct exponent
[Flow Exponent (2.15.3.2.)
(Page 236)] and breakpoints
[Universal Head versus Flow
(2.15.5.) (Page 241)].
For volume application: Verify
vessel dimensions. See Vessel
Shape (2.6.1.) (Page 184).
For flow application: Verify PMD
dimensions. See PMD Dimen-
sions (2.15.4.) (Page 239).
Program relay.
Verify with simulation. See Sim-
ulation (3.4.) (Page 262).
Verify with simulation. See Sim-
ulation (3.4.) (Page 262).
Verify setpoints.
Verify with simulation. See Sim-
ulation (3.4.) (Page 262).
Verify with simulation. See Sim-
ulation (3.4.) (Page 262).
Verify setpoints.
Set Transducer Enable (3.3.1.)
(Page 250) to ENABLED, then
request an echo profile.
Verify that each relay is as-
signed to one function only.
Review relay assignments
under Pumps (2.7.)
(Page 189) and Other Con-
trol (2.11.) (Page 216).
Verify that all 'ON' setpoints
are greater than their respec-
tive 'OFF' setpoints for pump
down applications (or vice
versa for pump up applica-
tions).
Ensure range set in Level
Setpoint Variation
(2.7.2.1.2) (Page 192) has
not caused 'ON' or 'OFF' set-
points to overlap.
279

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sitrans lut400

Table of Contents