Activating Sitrans Lut400 - Siemens SITRANS L 7ML5400 Operating Instructions Manual

Ultrasonic level controllers
Table of Contents

Advertisement

6.2

Activating SITRANS LUT400

Note
• Program Mode and Measurement mode refer to the display only. While the device is in
Program mode, the output remains active and continues to respond to changes in the
device.
• To enter Program mode using the device local push buttons, press
to Measurement mode.
• The display will return to Measurement mode after ten minutes of inactivity (from last
button press), when in Program Mode and from within a Wizard. Pressing
take you to the main navigation menu. (It will not return to the screen from which the
timeout occurred.).
1. Power up the device. SITRANS LUT400 automatically starts up in Measurement mode. A
transition screen showing first the Siemens logo and then the current firmware revision of
the LUI is displayed while the first measurement is being processed.
2. The first time the device is configured, you will be prompted to select a language (English,
German, French, Spanish, Chinese, Italian, Portuguese, or Russian). To change the language
again (after initial setup), see Language (6.) (Page 266).
3. Device time is set to Eastern Standard Time (EST) at the factory. To modify, see Date and
Time (Page 232). The correct date and time should be set prior to configuring the device.
SITRANS LUT400
Operating Instructions, 04/2021, A5E33329501-AG
Commissioning
6.2 Activating SITRANS LUT400
. Press
to return
will then
51