Ma Setpoint (2.5.3.); Ma Setpoint (2.5.4.) - Siemens SITRANS L 7ML5400 Operating Instructions Manual

Ultrasonic level controllers
Table of Contents

Advertisement

Parameter reference (LUI)
9.2 Setup (2.)
Refer to PMD supplier documentation for maximum head.
1)
To modify Current Output Function via SIMATIC PDM:
Open the menu Device – Select Analog Output.
9.2.5.3

4 mA Setpoint (2.5.3.)

Sets the process level corresponding to the 4 mA value. 4 mA always defaults to 0 m, and
Current Output Function (2.5.1.) (Page 180) determines the type of measurement. [See
Current Output Function (2.5.1.) (Page 180) for an illustration.]
Values
• Enter the reading that is to correspond to a 4 mA output.
• Units are defined in Units (2.1.1.) (Page 172) for Level, Space, Distance, or Head, and in
Flowrate Units (2.15.3.7.) (Page 238) for Flow. Volume units are converted from a level
value.
9.2.5.4

20 mA Setpoint (2.5.4.)

Sets the process level corresponding to the 20 mA value. 20 mA always defaults to 60 m, and
Current Output Function (2.5.1.) (Page 180) determines the type of measurement. [See
Current Output Function (2.5.1.) (Page 180) for an illustration.]
Values
• Enter the reading that is to correspond to a 20 mA output.
• Units are defined in Units (2.1.1.) (Page 172) for Level, Space, or Distance, or Head, and in
Flowrate Units (2.15.3.7.) (Page 238) for Flow. Volume units are converted from a level
value.
182
Range: Level, Space, Distance,
Head: 0.000 to 60.000 m
Volume: 0.0 to Max. Volume
Flow: 0 to Max. Flow
Default: 0
(set to value corresponding to 0% as defined by Current Output Function
and associated units)
Range: Level, Space, Distance,
Head: 0.000 to 60.000 m
Volume: 0.0 to Max. Volume
Flow: 0 to Max. Flow
Default: Level, Space, Distance,
Head: 60.000
Volume: Max. Volume
Flow: Max Flow
(set to value corresponding to 100% as defined by Current Output Function and
associated units)