Setting S1 and S2 switches at the remote site
Before installing a Fiber Remote Multi-IPE Interface unit:
•
•
Table 12 "Switch S1 and S2 settings" (page 77)
and their settings based on the Fiber Remote Multi-IPE Interface position
in the system.
Table 12
Switch S1 and S2 settings
For single Fiber Remote Multi-IPE
Fiber Remote Multi-IPE Interface at
Fiber Remote Multi-IPE Interface in
Note: Switch position: ON= Up and OFF= Down for S1 and S2 switches.
Table 13 "System monitor address selection" (page 78)
position 3-5 that represent the system monitor address numbers from 0 to
63 at the remote site.
Copyright © 2007-2009 Nortel Networks
.
configure the Fiber Remote Multi-IPE Interface using S1 and S2
dip-switches
install redundant fiber-optic connectors, if required
Function selection
Interface unit
the MMI terminal or modem end
of the daisy-chain
the middle of the daisy-chain
Fiber Remote Multi-IPE Interface
system monitor address
Physical location of the Fiber
Remote Multi-IPE Interface
Reserved for future use
Nortel Communication Server 1000
Fiber Remote Multi-IPE Interface Fundamentals
NN43021-556 03.01
Switch and
Position
S1 Position 1
and Position 2
S1 Position 1
Position 2
S1 Position 1
Position 2
S1 Positions
S2 Position 1
S2 Positions
11 May 2009
Remote IPE installation 77
lists switches S1 and S2
Switch setting
ON (at local and
remote sites)
ON
OFF
OFF
OFF
Refer to
3-8
Table 10 "Fiber
Remote Multi-IPE
Interface and
system monitor
address selection
table" (page 50)
ON-Remote site
OFF
3-8
shows S1 switch