Omron sysmac NX102-9 Series Owner's Manual page 208

Machine automation controller, cpu unit built-in ethernet/iptm port
Table of Contents

Advertisement

7 Tag Data Link Functions
1
Click the Connections Tab, and then click the Edit All Button. The following Edit All Connec-
tions Dialog Box is displayed.
The settings are as follows:
Setting
Target Device
Connection Name
Connection I/O Type
In/Out
Target Variable
Originator Variable
Connection Type
7-40
Select the target device.
Any name can be given to the connection (32 single-byte characters max.).
If this field is left blank, a default name is assigned. The connection name is
used as a comment.
Select Input Only (tag type) to use tag data links with a CS1W-EIP21, CJ1W-
EIP21, CJ2B-EIP21, CJ2M-EIP21, CJ1W-EIP21(CJ2), CJ1W-EIP21(NJ),
NX701, NX102-, NX1P2, NJ501-, NJ301-, or NJ101.
When you create tag data links for other devices, select the connection I/O
type specified in that device's EDS file. Use the Input Only (ID type) setting
when another company's node is the originator and does not support connec-
tion settings with a Tag type setting.
The connections I/O is automatically displayed based on the selected con-
nection.
• Input Only: Just In is displayed.
Select the target node's tag set to assign it.
• In: Select the target's output (produce) tag set.
• Out: Select the target's input (consume) tag set.
Select the originator node's tag set to assign it.
• In: Select the originator's input (consume) tag set.
• Out: Select the originator's output (produce) tag set.
Select whether the data is sent in multi-cast or unicast (point-to-point) form.
The default setting is multi-cast.
• Multi-cast connection:
Select when the same data is shared by multiple
• Point-to-point connection: Select when the same data is not shared by mul-
Note Refer to 7-1-4 Overview of Operation for details on using multi-cast and
unicast connections, and counting the number of connections.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Description
nodes. This setting is usually used.
tiple nodes. In a unicast connection, other
nodes are not burdened with an unnecessary
load.

Advertisement