Tcp/Udp Message Service; Outline Of Tcp/Udp Message Service; Specifications Of Tcp/Udp Message Service; Settings Required For Tcp/Udp Message Service - Omron sysmac NX102-9 Series Owner's Manual

Machine automation controller, cpu unit built-in ethernet/iptm port
Table of Contents

Advertisement

9 Socket Service
9-8

TCP/UDP Message Service

9-8-1

Outline of TCP/UDP Message Service

TCP/UDP socket communication to enable simple access to the CIP object of the Controller from sys-
tems which do not support EtherNet/IP is possible. This enables change of settings and I/O control of
the units connected to the Controller and NX bus. The service can be executed simultaneously with the
tag data link communications.
This service can only be used on the NX102 CPU Unit.
9-8-2

Specifications of TCP/UDP Message Service

Item
Maximum number of clients which
can be connected simultaneously
Maximum message size
Maximum NX data output size
Maximum NX data input size
Port number
9-8-3

Settings Required for TCP/UDP Message Service

When you use the TCP/UDP message service, you need to set the following unit settings.
This setting can be set to the Sysmac Studio version 1.23 or higher.
Sysmac Studio
Unit Settings Tab
Page
TCP/UDP mes-
sage service
*1 When you use the TCP socket, the following ports are used by the system and cannot be set by the user: 20,
23, 25, 80, 110, 9610, and 44818.
When you use the UDP socket, the following ports are used by the system and cannot be set by the user: 25,
53, 68, 110, 2222, 2223, 2224, 9600, and 44818.
9-32
32 (UDP and TCP respectively)
Request: 492 bytes
Response: 496 bytes
Maximum size of NX output data which can be written with the TCP/UDP
message service
488 bytes
Maximum size of NX input data which can be read with the TCP/UDP mes-
sage service
496 bytes
Port number used in the TCP/UDP message service
Default value: 64000 (decimal number)
Setting
Use/Do not use TCP/UDP
message service
Port 1-Port No.
Port 2-Port No.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Specifications
Setting condi-
Setting range
tions
Optional
Use/Do not use
Optional
1024-65535
Optional
1024-65535
Default
Do not use
*1
64000
*1
64000

Advertisement

Table of Contents
loading

Table of Contents