Example Of Nx Unit Setting Using Nx Configuration Object Service; A-8-1 Changing The Unit Operation Settings For Singe Nx Unit; Changing The Unit Operation Settings For Singe Nx Unit; Changing The Unit Operation Settings For Multiple Nx Units - Omron sysmac NX102-9 Series Owner's Manual

Machine automation controller, cpu unit built-in ethernet/iptm port
Table of Contents

Advertisement

A-8
Example of NX Unit Setting Using NX
Configuration Object Service
You can change the NX Unit settings by using the NX Configuration object service.
This section describes the examples of the procedure for NX Unit setting using the NX Configuration
object service.
Refer to 8-5-3 NX Configuration Object (Class ID: 74 hex) for details on the NX Configuration object.
The following three types of procedure examples are given.

• Changing the Unit operation settings for singe NX Unit.

• Changing the Unit operation settings for multiple NX Units.

• Initializing the Unit operation settings for singe NX Unit.
Precautions for Correct Use
Precautions for Correct Use
Refer to 16-2 Checking Status with the Network Configurator for troubleshooting errors that
occurred while setting NX Units using the NX Configuration object service.
Version Information
You can use the NX Configuration object to set an NX Unit only for the NX102 CPU Units.
A-8-1
Changing the Unit Operation Settings for Singe NX Unit
Change the Unit operation settings for single NX Unit mounted to the Controller. In this example, the
unit number of the relevant NX Unit is 1.
The following table gives the setting procedure.
Procedure
number
1
Change the parameter write
mode of the NX Unit to Write
mode.
2
Write values to the NX object of
the NX Unit.
3
Save the values that were set in
the NX Unit.
4
Restart the NX Unit.
NJ/NX-series CPU Unit Built-in EtherNet/IP Port User's Manual (W506)
Description
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
0x74
NX Configuration
object
Used CIP object
Instance
Class ID
ID
0x01
0x37
Switch parameter
write mode
0x01
0x34
Write NX object
0x01
0x36
Save parameter
0x01
0x35
Restart NX unit
Appendices
Unit
Service code
number
0x01
0x01
0x01
0x01
A-69
A