Connecting the unit

6.2.1 Adjusting the unit to the supply voltage

DANGER
NOTICE
28
If the unit is connected to electrical supply mains without a neutral
conductor, a type B fault current circuit breaker (RCD type B), which is
sensitive to all types of current, must be installed.
The unit generates a small fault current through use of special
electronic components. To ensure that the residual current device does
not trip during normal operation, each unit should have its own residual
current device.
Potential equalization
Image: Potential equalization symbol
The unit can be included in a potential equalization system by means of
appropriately sized wiring.
Risk of personal injury and property damage from electric shock
• Prior to working on the Platinum Combi Team , ensure that the
two electrical circuits inside the unit are de-energized.
• Do not operate the unit with the housing open.
Risk of property damage from wrong supply voltage
• Prior to connecting, measure the supply voltage and check the voltage set
on the transformer inside the unit.
The unit is set to a specific supply voltage or voltage range when
delivered.
If the voltage on site differs from the preset supply voltage, damage
may occur.
Prior to connecting the unit, you must measure the supply voltage,
check the transformers in the unit and reposition the connections if
necessary.
Installation instructions