SmartLi 1.0
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0612-1
Battery module
fault
0612-2
Battery module
fault
0021-5
Battery EOD
Issue 08 (2022-11-15)
Severity
Critical
Critical
Critical
Copyright © Huawei Digital Power Technologies Co., Ltd.
A
Cause
● The sampling
connecter is
not firmly
connected.
● The board
sampling
circuit of the
battery module
is faulty.
● The battery
module is
faulty.
● The sampling
connecter is
not firmly
connected.
● The board
sampling
circuit of the
battery module
is faulty.
● The battery
module is
faulty.
The battery
voltage reaches
the EOD threshold
due to continuous
discharge.

A Alarm List

Alarm List
Solution
Replace the faulty battery
module.
Replace the faulty battery
module.
1. Check the status of the
battery cabinet and turn
on the battery switch.
2. Check the input source and
charge batteries in a timely
manner.
107