SmartLi 1.0
User Manual
Item
RS485 port
address
RS485 port
baud rate
COM port
address
COM port
baud rate
ModbusTCP
encryption
SSH
IP address allocation
Issue 08 (2022-11-15)
Description
Specifies the address for
RS485 communication.
Matches the user's network
management conditions
onsite.
Specifies the address for
COM communication.
Matches the user's network
management conditions
onsite.
If Modbus TCP is used for
communication,
communication links do not
implement encryption or
implement encryption based
on the selected encryption
mode.
Channel protocol for logging
in to the back end.
If the MDU is directly connected to a computer, the IP address can only be
allocated manually. The IP addresses of the MDU and computer must be in
the same network segment, and must be different.
If the MDU is connected to a computer through a LAN switch or router with
the DHCP function, the IP address can be allocated manually or automatically.
Manual allocation is used by default.
Manual: Check that their IP addresses are two different values on the
same network segment. Set the SmartLi IP address to be in the same
subnet as the PC IP address. Perform the bitwise AND operation for the
UPS IP address and the PC IP address with the subnet mask respectively.
If the operation results are the same, the two IP addresses are in the
same subnet.
AND operation rule: 1 AND 1 = 1, 1 AND 0 = 0, 0 AND 1 = 0, 0 AND 0 =
0. That is when the corresponding bits are both 1, the result is 1. In other
cases, the result is 0.
Copyright © Huawei Digital Power Technologies Co., Ltd.
4 User Interface
Default
Value Range
Value
1
1-254
9600
4800, 9600,
19200, 115200
80
1-254
9600
4800, 9600,
19200, 115200
Disable
Disable, Enable
Disable
Disable, Enable
63