Figure 5-6 Removing control cables
Step 5 On the home screen, choose Settings > System Settings, and set Battery cabinet
quantity to 4.
----End

5.7 Testing Batteries

5.7.1 Shallow Discharge Test

Before performing a shallow discharge test, ensure that:
● The UPS is working in normal mode; float charging or hibernation has lasted
● The UPS generates no battery overtemperature, overvoltage, or overcurrent
● The mains, batteries, charger, and discharger are normal. No overload alarm is
● The SmartLi has generated no alarms related to lithium batteries.
Issue 08 (2022-11-15)
NO TICE
for 2 hours after the state of charge (SOC) reaches 100%; and the load ratio
fluctuation is less than 10%.
alarm. No generator is connected to the UPS.
generated.