Huawei SmartLi 1.0 User Manual page 115

Hide thumbs Also See for SmartLi 1.0:
Table of Contents

Advertisement

SmartLi 1.0
User Manual
Alarm ID
Alarm Name
(Alarm ID-
Cause ID)
0024-2
Battery
undertemperatur
e
0023-2
Battery
overtemperature
0025-2
Battery
overvoltage
0026-4
Battery
undervoltage
0616-1
Battery
undertemperatur
e protection
0031-2
Battery
overtemperature
protection
0032-3
Battery
overvoltage
protection
0617-1
Battery
undervoltage
protection
0612-5
Battery module
fault
Issue 08 (2022-11-15)
Severity
Minor
Minor
Minor
Minor
Critical
Critical
Critical
Critical
Critical
Copyright © Huawei Digital Power Technologies Co., Ltd.
Cause
The cell
temperature is too
low.
The cell
temperature is too
high.
The cell voltage is
too high.
The cell voltage is
too low.
The charger
temperature is too
low.
The battery
temperature is too
high.
The voltage of a
single cell is too
high.
The cell is
overdischarged.
● The sampling
connecter is
not firmly
connected.
● The board
sampling
circuit of the
battery module
is faulty.
● The battery
module is
faulty.
A Alarm List
Solution
Take measures to increase the
ambient temperature.
Take measures to reduce the
ambient temperature.
1. Check the power cabinet
status.
2. Check the lithium battery
cabinet status.
Check the power cabinet
status.
Take measures to increase the
ambient temperature.
Take measures to reduce the
ambient temperature.
1. Check the power cabinet
status.
2. Check the lithium battery
cabinet status.
Check the power cabinet
status.
Replace the faulty battery
module.
108

Advertisement

Table of Contents
loading

Table of Contents