SmartLi 1.0
User Manual
● The BCB off alarm is displayed on the UPS LCD and SmartLi LCD. No action is
● After the battery control unit is started, the green indicator is on for 1s and
● If multiple SmartLi cabinets are combined, press and hold the POWER ON/OFF
Step 3 Set the language, time, date, network parameters, and system parameters on the
Settings Wizard screen
Figure 5-1 Settings wizard
Step 4 After the green indicator of the battery control unit blinks at 10 Hz, turn on the
battery circuit breaker on the SmartLi.
● If the green indicator of the battery control unit blinks at 10 Hz, you cannot
● If the green indicator of the battery control unit blinks at 1 Hz or is steady on,
Issue 08 (2022-11-15)
NO TICE
required. After the battery circuit breaker is closed, the alarm is automatically
cleared.
then off for 4s, and the red indicator is steady on.
button on each battery control unit of the cabinets one by one for more than
2s.
NO TE
In a parallel system, Battery cabinet quantity indicates the total number of battery
cabinets.
NO TICE
start the UPS in cold mode.
you can start the UPS in cold mode.
Copyright © Huawei Digital Power Technologies Co., Ltd.
5 Operations
77