Energy Packs; Energy Pack Compatibility; Pacsystems Rxi Energy Pack (Icrxiaccepk01A); Specifications - GE GFK-2741C Manual

Pacsystems controllers battery and energy pack
Table of Contents

Advertisement

Energy Packs

3.
An Energy Pack is used in conjunction with a Controller to preserve user memory in the Controller during power
fluctuations or outages.
If system power is lost, the Energy Pack maintains power long enough for a Controller to write its user memory
contents to non-volatile memory. When system power is restored, the user memory is restored if the Controller is
configured to power up from RAM.

Energy Pack Compatibility

3.1
The correct Energy Pack must be used with the corresponding controller. Do not attempt combinations except
those shown as "compatible" in the table below:
Energy Pack
IC695ACC400
Cap Pack
IC695ACC400
Controller
ICRXICTL000
Incompatible
IC695CPE305
Compatible
IC695CPE310
IC695CPE330
Incompatible

PACSystems RXi Energy Pack (ICRXIACCEPK01A)

3.2
3.2.1

Specifications

Part Numbers
ICRXIACCEPK01A
Energy Pack. Includes base, Cap Pack module and Energy Pack to Controller cable
ICRXIACCCPK01A
Replacement Cap Pack module
ICRXIACCCBL01A
Replacement 0.3m (12") Energy Pack to Controller cable
Functional Specifications
Dimensions
Input voltage range
Input power, maximum
Output voltage range
Output power maximum
Output current maximum
Backup trip voltage
Capacitor Pack life expectancy
Environmental Specifications
The Energy Pack shall be installed in a location that is not exposed to corrosive gases or liquids, rain, or direct
sunlight, and that meets the environmental specifications listed below.
Operating Temperature, surrounding air
Storage Temperature
Humidity
Environment
GFK-2741C
IC695ACC402
ICRXIACCEPK01A
IC695ACC412
ICRXIACCCPK01A
Incompatible
Compatible
Incompatible
Incompatible
Compatible
Incompatible
114.05 × 77.47 × 63.75 mm
(4.49" × 3.05" × 2.51")
20–30 Vdc
36 W + connected device power requirement
18–30Vdc
45 W
2.25 A
19 Vdc ±4%
5 years
-25˚C to 60˚C
-40C to +85C (-40°F to 185°F)
5% to 95%, non-condensing
Restricted Access Area and Pollution Degree 2 environment as defined below.