ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual page 99

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
after the cancellation of the blocking. The "Deactivated" setting causes that no input value
to be evaluate after cancellation of the blocking.
12.32.7
Extended parameter – Behavior output after return of voltage
Options
The parameter "Behavior output after return of voltage" exists to permit a defined
behavior at the "Output" communication object after a return of voltage. A determination
is made here about whether the "Output value upper threshold" or the "Output value
lower threshold" is sent out on the output object. The "Deactivated" setting causes no
telegram to be sent out after return of voltage.
Deactivate
Output value upper threshold
Output value lower threshold
98