ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual page 58

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
12.15.2
Common parameter – Reaction for short operation
Options
Here it is specified whether the "Value 1" or the "Value 2" is sent out for a short operation
of the button. Alternatively, Value1/Value2 can also be alternatingly set for a short
operation, i.e. after Value 1 was sent (or received), a renewed operation will send out a
Value 2. After it is operated again, Value 1 is again sent out. The "No reaction" setting
causes no telegram to be sent out for a short operation of the button.
12.15.3
Common parameter – Reaction for long operation
Options
Here it is specified whether the "Value 1" or "Value 2" is sent out for a long operation of
the button. Alternatively, Value1/Value2 can also be alternating set for a long operation,
i.e. after Value 1 was sent (or received), a renewed operation will send out a Value 2.
After it is operated again, Value 1 is again sent out. The "No reaction" setting causes no
telegram to be sent out for a long operation of the button.
12.15.4
Extended parameter – Duration of long operation (ss:ms)
Options
A differentiation can be made between a short or long operation of the button. With a
short operation of the button, the next level forward is switch to in each case. With a long
operation, the first level is activated. Thus, with a long button press a jump back from
every position to the first level is possible, without having to run through the remaining
levels.
Via the "Duration of long operation", the time is specified from which a long button press
is recognized, and the object values are reset. The first level must be set again with a
press of the button. Any time from 0.3 to 3 seconds can be set. A typical value after which
a jump-back to level 1 is set at 0.4 s.
12.15.5
Extended parameter – Value 1 for short operation
Options
Note": This parameter is only visible if the "Reaction at short operation"
parameter is set on either "Value 1" or "Alternating Value1/Value2".
No reaction
Value 1
Value 2
Alternating value1/value2
No reaction
Value 1
Value 2
Alternating value1/value2
Time input from 0.3 to 3.0 seconds
Off
On
57