Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
Activating this parameter will cause the manual adjustment to be deleted and the new
setpoint value to be provided when a new value is received via the "Basic setpoint" object.
If the parameter is deactivated, the manual adjustment is add to the new base setpoint
value.
Example: Previous base setpoint value of 21°C + manual adjustment of 1.5°C = 22.5°C.
The object receives a new basic setpoint of 18°C plus the previous manual adjustment of
1.5°C for a total of 19.5°C.
12.34.93
Changing set value – Resetting of the manual adjustment for change of
operating mode
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
If the device switches to a new operating mode, the manual adjustment is deleted and
the parameterized setpoint temperature for the operating mode plus any change by the
base setpoint value object will be applied if this parameter is activate. Example: Comfort
temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. Change to Eco with
programmed temperature 17°C. The device regulates the temperature to 17°C, since the
manual adjustment is deleted.
If the parameter is deactivated, the manual setpoint adjustment will be added to the
temperature in the new operating mode.
Example: Comfort temperature of 21°C plus manual adjustment of 1.5°C = 22.5°C. If the
system switches to Eco with a parameterized temperature of 17°C, the device regulates
the temperature to 18.5°C, since the manual adjustment is added.
No
Yes
134