ABB i-Bus
®
KNX Yucus

Application "General"

12.2
General setting of control element rocker configuration, Left/Right individual – 1 button or
Left/Right pair – 2 buttons, in operation and locking function
12.2.1 General – Send cyclic "In operation" object
Options
This parameter is used to specify the "In operation" communication object serves to
inform that the controller still operates. Value "1" is sent cyclic. This parameter is used to
set the cycle for sending. If the cyclic telegram fails, the function of the control element is
faulty, and for RTC version. The air-conditioning of the room can be maintained with a
forced operation. However, for this the system and/or actuator must have "Forced
operation" function.
12.2.2 General – Send cyclic "In operation" time (min)
Options
This parameter is used to specify define the interval time of sending cyclic.
12.2.3 Common parameter – Row 1/2/3/4
Options
This parameter is used to specify the button configuration of the rocker.
Left/Right individual – 1 button: Rocker will be split into 1
Individual button will have its own assign application that make a set of parameters and
communication objects. When the 1
telegram is sent out.
Left/Right pair – 2 buttons: Rocker will function as "rocker total", Both left and right button
will have the same assign application that make a set of parameters and communication
objects. When either left or right button is actuated or release, a telegram is sent out. It
does not differentiate here between whether the rocker is operated on the left or right
button.
12.2.4 Common parameter – Locking function selection
Options
This parameter is used to specify whether or not to activate the locking function selection.
When function locking is selected, 1 bit communication object is to be activated in the
individual button parameter. It is used to control the locking function of individual rocker
function
Send value "0" cyclically
Send value "1" cyclically
Time input from 5 min to 3000 min
Inactive
Left/Right individual – 1 button
Left/Right pair – 2 button
st
nd
(left) or 2
(right) button is actuated or release, a
Inactive
Function locking
Device locking
st
(left) and 2
nd
(right) button.
29