ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual page 154

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
12.35.14
Control of heating additional stage - Object no
Object name
Additional heating stage
Additional hating stage
-
1 bit: This object is used to operate a switching actuating drive, e.g. a
thermoelectric positioner that is controlled by a switching/heating actuator.
-
1 byte This object is use to control an actuating drive with a continuous input value
(0%..100%), e.g. an electromotive actuating drive.
12.35.15
Control cooling - Object no
Object name
Cooling control value
Cooling control value
-
1 bit: This object is used to operate a switching actuating drive, e.g. a
thermoelectric positioner that is controlled by a switching/heating actuator.
-
1 byte This object is use to control an actuating drive with a continuous input value
(0%..100%), e.g. an electromotive actuating drive.
12.35.16
Control cooling – Basic stage cooling – Object no
Object name
Status cooling
The room temperature controller sends an ON telegram via the "Cooling status" object as
soon as it is active in the cooling mode. If the controller is in the inactive zone between
heating and cooling or is in heating mode, the room temperature controller transmits an
OFF telegram on the "Cooling status" object.
12.35.17
Control of cooling additional stage - Object no
Object name
Additional cooling stage
Additional cooling stage
-
1 bit: This object is use to operate a switching actuating drive, e.g. a thermoelectric
positioner that is controlled by a switching/heating actuator.
-
1 byte This object is use to control an actuating drive with a continuous input value
(0%..100%), e.g. an electromotive actuating drive.
12.35.18
Setting of basic load – Object no
Object name
Basic load
This object uses the value 1 to activate a parameterized base load, i.e. a minimum control
value greater than zero. The value 0 deactivates the base load. When the base load is
deactivated, the control value can be lowered all the way to zero if necessary when the
setpoint temperature is reach, despite the minimum value set in the parameter.
Data type
1 bit DPT 1.001
1 byte DPT 5.001
Data type
1 bit DPT 1.001
1 byte DPT 5.001
Data type
1 bit DPT 1.001
Data type
1 bit DPT 1.001
1 byte DPT 5.001
Data type
1 bit DPT 1.001
Flags
C, T
C, T
Flags
C, T
C, T
Flags
C, T
Flags
C, T
C, T
Flags
C, W, T, U
153