ABB i-bus KNX Yucus YUB/U1.0.1 Series Technical Reference Manual page 136

Knx sensor control element 1/2-fold/2/4-fold/3/6-fold/4/8-fold, fm, knx sensor room temperature controller/with 2/4-fold control element, fm
Table of Contents

Advertisement

KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
12.34.94
Changing set value – Resetting the manual adjustment via object
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
If this parameter is activated, a separate object can be used to delete the manual
adjustment at any time. Example of application: Resetting the manual adjustment on all
devices located in a building using a system clock.
12.34.95
Changing set value – Permanent storage of onsite operation
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
If this parameter is activated, the manual settings for setpoint and, where applicable, fan
speed level, as well as the value of the "Basic load" object, will be stored in the device
and re-activated after a reset. If the device is re-programmed, the stored setpoint values
will also be deleted.
12.34.96
Temperature reading – Input of temperature reading
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device".
The room temperature can be measure at the device or fed to the device by an object via
the bus. In addition, weighted measuring is also available, in which the weighted average
of up to three temperature values (1 x internal, 2 x external) is calculated and used as an
input value for control.
No
Yes
No
Yes
Internal measurement
External measurement
Weighted measurement
135

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents