KNX Technical Reference Manual
ABB i-Bus
®
KNX Yucus
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on "Heating",
"Heating with additional stage", "Heating and cooling" or "Heating and cooling with
additional stages".
Function for protecting the building against the cold. On devices with a display, this mode
is indicated by the frost protection symbol. Manual operation is lock.
12.34.80
Setpoint setting – Setpoint temperature for cooling comfort (°C)
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on "Cooling",
"Cooling with additional stage", "Heating and cooling" or "Heating and cooling with
additional stages", only available when "Setpoint heating comfort = Setpoint cooling
comfort" parameter is set on "No".
Specifies the comfort temperature for cooling when people are present.
12.34.81
Setpoint setting – Increase for standby cooling (°C)
Options
Note: Only available when the "Device function" parameter is set on either
"Single device" or "Master device" and the Control function parameter is set on "Cooling",
"Cooling with additional stage", "Heating and cooling" or "Heating and cooling with
additional stages".
Specifies the temperature in cooling mode when nobody is present. On devices with a
display, this mode is indicated by the standby symbol.
12.34.82
Setpoint setting – Increase for ECO cooling (°C)
Options
Input from 10 to 40
Input from 0 to 15
Input from 0 to 15
130